Technical Specifications

Standard Specifications

Parameter

Units

Specification

Treated Water Volume 75,000 L per vessel (based on 60 µm/cm2 feed water)
Vessel Sizemm1,500 H 300 D
Flow RateL/hr1,300 (nominal)
Feed Water Conductivityµs/cm<60 (typical)
Treated Water Conductivityµs/cm<3 (typical)
Raw Water Temperature°C15 ~ 35
Feed Water Inlet PressurekPa>150<500 (typical)
Treated Water Discharge Pressure DropkPa~50 (typical)
Power Supply-Single phase, 240 V

Standard Inclusions and Options

= Standard Supplyo = Optional Supply- = Not Applicable

Equipment

MAKPAK

Two MAKPAK Deionisation Vessles
Header Pipework and Barrel Union
Manual Isolation Valves
Pre-treatment – Activated Carbono

Instrumentation

Standard Package

Yes / No Indicator
Pressure Gaugeso
Flow Gauges (Rotameters)o
Pressure Transmitters (4-20 mA)-
Flow Transmitters (4-20 mA)o
Conductivity Transmitter (4-20 mA)o

NOTE: Output from 4-20mA transmitters to connected to the control system by others.